5
EA-PSI 10200-210 3U 为德国EA较新推出的高精度直流电源,在进口直流电源中被广泛用于汽车测试电源等领域。
EA-PSI 10200-210 3U 为德国产品技术规格书(点击右键另存为)德国EA代理,上海雨芯仪器科技有限公司提供
Features
Wide range input, 208 V - 480 V +10 % 3ph AC
Active Power-Factor-Correction, typical 0.99
Very high efficiency up to 96 %
High performance of 15 kW per unit
Voltage from 0 - 60 V up to 0 - 2000 V
Currents from 0 - 20 A up to 0 - 510 A
Flexible power regulated DC output stages
(autoranging)
Regulation mode CV, CC, CP, CR with fast crossover
Digital regulation, high resolution with 16bit ADCs and DACs, selection of control speed: Normal, Fast, SlowColor 5“ TFT display with touch control and intuitive user interface
Galvanically isolated Share-Bus for parallel operation of all power classes in the 10000 series
Master-Slave bus for parallel operation of up to 64 units of all power classes in the 10000 series
Integrated function generator with predefined curvesPredefined automotive test procedures for LV123, LV124 and LV148
Command langes and drivers: SCPI and ModBus, LabVIEW, IVI
Build-in Interfaces
USB
Ethernet
Analog
USB Host
Master-Slave-Bus
Share-Bus
Optional Interfaces
CAN
CANopen
RS232
Profibus
EtherCAT
Profinet, with one or two ports
Modbus, with one or two ports
Ethernet, with one or two ports
Software
EA-Power Control
Technical Specifications EA-PSI 10200-210 3U DC-Output Voltage range 0 - 200V Ripple rms CV ≤40 mV BW 300 kHz Ripple and noise p-p CV ≤300 mV BW 20 MHz Current range 0 - 210 A Power range *1 0 - 15000 W Resistance range 0.033 Ω - 50 Ω Output capacity 7560 μF Efficiency up to 94.5% *1 Isolation Negative DC-Pol <-> PE ±1000 V DC Positive DC-Pol <-> PE +1000 V DC Article number 06230822
*1 ** Power and ** Output voltage
EA-PSI 10200-210 3U
General specifications
AC-Input Voltage, Phases 208 V / 380 V / 400 V / 480 V ±10%, 3ph AC (208 V 3ph AC with Derating to 9 kW) Frequency 45-66 Hz Power factor >0.99 Leakage current < 5mA Overvoltage category 2 Pollution degree 2 DC-Output static Load regulation CV ≤0.05% FS (0 - ** load, constant input voltage and constant temperature) Line regulation CV ≤0.01% FS (110 V - 240 V AC +10% input voltage, constant load and constant temperature) Stability CV ≤0.02% FS (Over 8hrs interval following 30 minutes warm-up, constant input voltage, load and temperature) Temperature coefficient CV ≤30ppm/°C (Following 30 minutes warm up) Compensation (Remote Sense) ≤5% UNominal Load regulation CC ≤0.1% FS (0 - ** load, constant input voltage and constant temperature) Line regulation CC ≤0.01% FS (208 V - 480 V AC +10% input voltage, constant load and constant temperature) Stability CC ≤0.02% FS (Over 8hrs interval following 30 minutes warm-up, constant input voltage, load and temperature) Temperature coefficient CC ≤50ppm/°C (Following 30 minutes warm up) Load regulation CP ≤0.3% FS (0 - ** load, constant input voltage and constant temperature) Load regulation CR ≤0.3% FS + 0.1% FS current (0 - ** load, constant input voltage and constant temperature) Protective functions OVP Overvoltage protection adjustable, 0 - 110% UNominal OCP Overcurrent protection adjustable, 0 - 110% INominal OPP Overpower protection adjustable, 0 - 110% PNominal OT Overtemperature protection, output shuts down in case of insufficient cooling DC-Output dynamic Rise time 10 - CV ≤20 ms Fall time 90 - 10% CV ≤20 ms Rise time 10 - CC ≤10 ms Fall time 90 - 10% CC ≤10 ms Display accuracy Voltage ≤0.05% FS Current ≤0.1% FS Insulation AC-Input to DC-Output 3750 Vrms (1 Minute), creepage >8 mm AC-Input to case (PE) 2500 Vrms DC-Output to case (PE) Depending on the model, see model table DC-Output to Interfaces 1000 V DC (Model up to 360 V output), 1500 V DC (Model from 500 V output) Interfaces Digital Built-in, galvanically isolated USB, Ethernet (100 MBit) for communication
1x USB Host for data acquisitionOptional, galvanically isolated CAN, CANopen, RS232, ModBus TCP, Profinet, Profibus, EtherCAT, Ethernet Interfaces Analog Built-in, galvanically isolated 15-pole D-Sub Signal range 0 - 10 V or 0 - 5 V (switchable) Inputs U, I, P, R, remote control on/off, DC output on/off, resistance mode on/off Outputs Monitor U and I, alarms, reference voltage, status DC, status CV/CC Accuracy U / I / P / R 0 - 10 V ≤0.2%, 0 - 5 V ≤0.4% Device configuration Parallel operation Up to 64 units of any power class in series 10000, with Master-Slave-Bus and Share-Bus Safety and EMC Safety EN 61010-1
IEC 61010-1
UL 61010-1
CSA C22.2 No 61010-1
BS EN 61010-1EMC EN 55011, class B
CISPR 11, class B
FCC 47 CFR Part 15B, Unintentional Radiator, class B
EN 61326-1 include tests according to:
- EN 61000-4-2
- EN 61000-4-3
- EN 61000-4-4
- EN 61000-4-5
- EN 61000-4-6Safety protection class 1 Ingress Protection IP20 Environmental conditions Operating temperature 0 - 50 °C Storage temperature -20 - 70 °C Humidity ≤80% RH, non-condensing Altitude ≤2000 m (≤6600 ft) Mechanical construction Cooling Forced air flow from front to rear, temperature controlled fans Dimensions (B x H x T) 19“ x 3U x 668 mm (Enclosure only, not over all) Weight 32.8 kg (72 lb)